--  Avocent ACS MIB
--  Copyright 2009 Avocent Corporation
--  Revision: 2.0.1
--  Last Modified: October 10, 2010
--------------------------------------------------------------------------------

ACS-MIB DEFINITIONS ::= BEGIN

IMPORTS
   Gauge,TimeTicks,IpAddress,Counter,NetworkAddress
      FROM RFC1155-SMI
  PhysAddress
      FROM RFC1213-MIB
  enterprises, MODULE-IDENTITY
      FROM SNMPv2-SMI 
  OBJECT-TYPE, MODULE-IDENTITY, OBJECT-IDENTITY, Integer32
      FROM SNMPv2-SMI
  DisplayString
      FROM SNMPv2-TC
  InterfaceIndex, InterfaceIndexOrZero
        FROM IF-MIB
   TRAP-TYPE
      FROM RFC-1215;

--------------------------------------------------------------------------------
-- Object Groupings
--------------------------------------------------------------------------------

--@ Note: every product type should be uniquely identified underneath the
--@ acsProducts object group. Each product should report its unique acsProducts
--@ OBJECT IDENTIFIER in mib-2.system.sysObjectID. Please see the file
--@ "_Avocent Enterprise Object Identifier Assignment.txt" for a list of the
--@ IDs that have been assigned.

-- enterprises  .1.3.6.1.4.1

-- avocent         OBJECT IDENTIFIER ::= { enterprises 10418 }

acs     MODULE-IDENTITY
        LAST-UPDATED    "201010100000Z"
        ORGANIZATION    "Avocent Corporation"
        CONTACT-INFO    "postal : Avocent Corporation
                                  47281 Bayside Parkway
                                  Fremont, CA 94538, USA
                         e-mail : Technical Support
                                  techsupport@avocent.com"
        DESCRIPTION        
        "This module defines the Avocent MIB extensions to 
         ACS60xx products."
	REVISION	"201010100000Z"
	DESCRIPTION	"Add products acs6004 and acs6008"
        REVISION        "200912110000Z"
        DESCRIPTION     "Extended acsPowerMgmt to support data monitoring 
                         and Avocent PM-PDUs"
        REVISION        "200709170000Z"
        DESCRIPTION     "First Draft"
::= { enterprises 10418 16 }

acsProducts     OBJECT IDENTIFIER ::= { acs 1 }
acsManagement   OBJECT IDENTIFIER ::= { acs 2 }
--
acs6016         OBJECT IDENTIFIER ::= { acsProducts 1 }    -- 10418.16.1.1
acs6032         OBJECT IDENTIFIER ::= { acsProducts 2 }    -- 10418.16.1.2
acs6048         OBJECT IDENTIFIER ::= { acsProducts 3 }    -- 10418.16.1.3
acs6004         OBJECT IDENTIFIER ::= { acsProducts 4 }    -- 10418.16.1.4
acs6008         OBJECT IDENTIFIER ::= { acsProducts 5 }    -- 10418.16.1.5

acsAppliance    OBJECT IDENTIFIER ::= { acsManagement 1  }  -- 10418.16.2.1
acsSessions     OBJECT IDENTIFIER ::= { acsManagement 2  }  -- 10418.16.2.2
acsSerialPort   OBJECT IDENTIFIER ::= { acsManagement 3  }  -- 10418.16.2.3
acsPowerMgmt    OBJECT IDENTIFIER ::= { acsManagement 5  }  -- 10418.16.2.5

-- objects under acsPowerMgmt
-- acsPowerMgmtNumSerialPorts 	::=  { acsPowerMgmt 1 } 
-- acsPowerMgmtSerialTable    	::=  { acsPowerMgmt 2 }
-- acsPowerMgmtPDUTable	      	::=  { acsPowerMgmt 3 }
-- acsPowerMgmtTotalNumberOfOutlets ::= { acsPowerMgmt 4 }
-- acsPowerMgmtOutletsTable   	::= { acsPowerMgmt 5 }
-- acsPowerMgmtNumberOfOutletGroup ::= { acsPowerMgmt 6 }
-- acsPowerMgmtGroupTable     	::= { acsPowerMgmt 7 }
-- acsPowerMgmtPhasesTable    	::= { acsPowerMgmt 8 } 
-- acsPowerMgmtBanksTable     	::= { acsPowerMgmt 9 } 
-- acsPowerMgmtEnvMonTable    	::= { acsPowerMgmt 10 } 
-- acsPowerMgmtOutElecMonTable 	::= { acsPowerMgmt 11 }


--
-- Note that traps are defined in a separate trap MIB 
--
acsTrapObject   OBJECT IDENTIFIER ::= { acsManagement 6 }  -- 10418.16.2.6

--
-- Type Definitions
--

--
-- Each enumeration represents the states of the appliance power supplies.
PowerSupplyState ::= INTEGER
{        
        statePowerOn(1),
        statePowerOff(2),
        powerNotInstaled(9999)
}

--
-- Each enumeration represents the speed of the serial port.
SerialPortSpeed ::= INTEGER
{
        speed300bps(300),
        speed600bps(600),
        speed1200bps(1200),
        speed2400bps(2400),
        speed4800bps(4800),
        speed9600bps(9600),
        speed19200bps(19200),
        speed38400bps(38400),
        speed57600bps(57600),
        speed115200bps(115200),
        speed230400bps(230400),
        speed460800bps(460800)
}

--
-- Each enumeration represents the state of the RS-232C signal.        
SerialPortSignalState ::=INTEGER
{
        up(1),
        down(2)
}

--
-- Each enumeration represents the RJ-45 pin-out
SerialPortPinOut ::=INTEGER
{
        cyclades(1),
        cisco(2)
} 

--
-- acsAppliance 
-- OBJECT IDENTIFIER ::= { acsManagement 1  }  10418.16.2.1
--
acsHostName OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "The appliance name"
::= { acsAppliance 1 }

acsProductModel OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..50) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "The appliance product model"
::= { acsAppliance 2 }

acsPartNumber OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "The part number of this appliance as shown on the label
         attached or imprinted on the appliance."
::= { acsAppliance 3 }

acsSerialNumber OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "The serial number of this appliance as shown on the label
         attached or imprinted on the appliance."
::= { acsAppliance 4 }

acsEIDNumber OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "The electronic ID number (EID) of this appliance as shown on the label
         attached or imprinted on the appliance."
::= { acsAppliance 5 }

acsBootcodeVersion OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "The version of the bootcode of this appliance."
::= { acsAppliance 6 }

acsFirmwareVersion OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "The version of the firmware of this appliance."
::= { acsAppliance 7 }

acsPowerSupply OBJECT-IDENTITY
        STATUS             current
        DESCRIPTION 
        "It gives information about Power Supply of this appliance"
::= { acsAppliance 8 }

acsPowerSupplyNumber OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "Number of the power supplies of this appliance"
::= { acsPowerSupply 1 }

acsPowerSupplyStatePw1 OBJECT-TYPE
        SYNTAX             PowerSupplyState
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "State of the first power supply"
::= { acsPowerSupply 2 }

acsPowerSupplyStatePw2 OBJECT-TYPE
        SYNTAX             PowerSupplyState
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "State of the second power supply"
::= { acsPowerSupply 3 }

acsReboot OBJECT-TYPE
        SYNTAX INTEGER {
                noAction(1),
                reboot(2)
             }
        MAX-ACCESS         read-write
        STATUS             current
        DESCRIPTION 
        "A set value of reboot(2) will reboot the appliance.
         noAction(1) = always returned in a GET. Does nothing if SET.        
         reboot(2)   = when SET the appliance immediately reboots."
::= { acsAppliance 9 }

--
-- acsSessions      
-- OBJECT IDENTIFIER ::= { acsManagement 2  }   10418.16.2.2
--
acsActiveSessionsNumberOfSession OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Number of active sessions."
::= { acsSessions 1 }

acsActiveSessionsTable OBJECT-TYPE
        SYNTAX             SEQUENCE OF AcsActiveSessionsTableEntry
        MAX-ACCESS         not-accessible
        STATUS             current
        DESCRIPTION
        "This table contains the list of active sessions."
::= { acsSessions 2 }
 
acsActiveSessionsTableEntry        OBJECT-TYPE
        SYNTAX            AcsActiveSessionsTableEntry
        MAX-ACCESS        not-accessible
        STATUS            current
        DESCRIPTION                
        "each entry has the information about the active session"
        INDEX        { acsActiveSessionsTableIndex }
::= { acsActiveSessionsTable 1 }

AcsActiveSessionsTableEntry ::= SEQUENCE  {
        acsActiveSessionsTableIndex        InterfaceIndexOrZero,     
        acsActiveSessionsTableUser         DisplayString, -- user name
	  acsActiveSessionsTableGroup        DisplayString, -- group name
        acsActiveSessionsTableType		 DisplayString, -- RO/RW-ssh,telnet or web 
        acsActiveSessionsTableConnection   DisplayString, -- type + target name
        acsActiveSessionsTableSessionTime  DisplayString, -- time of session
        acsActiveSessionsTableFrom         DisplayString, -- source of the session
        acsActiveSessionsTableKill         INTEGER
}

acsActiveSessionsTableIndex OBJECT-TYPE
        SYNTAX             InterfaceIndexOrZero
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "A unique index representing an entry in this table."
::= { acsActiveSessionsTableEntry 1 }

acsActiveSessionsTableUser OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "The name of the user that opens this session."
::= { acsActiveSessionsTableEntry 2 }

acsActiveSessionsTableGroup OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "The name of the group that the user belongs to."
::= { acsActiveSessionsTableEntry 3 }

acsActiveSessionsTableType OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "The session type."
::= { acsActiveSessionsTableEntry 4 }

acsActiveSessionsTableConnection OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "Connection type."
::= { acsActiveSessionsTableEntry 5 }

acsActiveSessionsTableSessionTime OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "Time of the session"
::= { acsActiveSessionsTableEntry 6 }

acsActiveSessionsTableFrom OBJECT-TYPE
        SYNTAX             DisplayString ( SIZE (0..32) )
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION 
        "The source IP address of the session."
::= { acsActiveSessionsTableEntry 7 }

acsActiveSessionsTableKill OBJECT-TYPE
        SYNTAX INTEGER {
                noAction(1),
                killSession(2)
             }
        MAX-ACCESS     read-write
        STATUS         current
        DESCRIPTION 
        "A set value of killSession(2) will kill the session.
          noAction(1)   = always returned in a GET. Does nothing if SET.
         killSession(2)= when SET the appliance immediately kills the session."
::= { acsActiveSessionsTableEntry 8 }

--
-- acsSerialPort     
-- OBJECT IDENTIFIER ::= { acsManagement 3  }   10418.16.2.3
--

acsSerialPortNumberOfPorts OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Number of Serial Ports (physical serial port plus Aux Port."
::= { acsSerialPort 1 }

acsSerialPortTable OBJECT-TYPE
        SYNTAX             SEQUENCE OF AcsSerialPortTableEntry
        MAX-ACCESS         not-accessible
        STATUS             current
        DESCRIPTION
        "This table contains information about serial ports."
::= { acsSerialPort 2 }
 
acsSerialPortTableEntry        OBJECT-TYPE
        SYNTAX            AcsSerialPortTableEntry
        MAX-ACCESS        not-accessible
        STATUS            current
        DESCRIPTION                
        "each entry has the information about specific serial port."
        INDEX            { acsSerialPortTableNumber }
::= { acsSerialPortTable 1 }

AcsSerialPortTableEntry ::= SEQUENCE  {
        acsSerialPortTableNumber          Integer32,    -- serial port number
        acsSerialPortTableDeviceName      DisplayString, -- associated device name
        acsSerialPortTableStatus          INTEGER,      -- status of serial port
        acsSerialPortTableName            DisplayString, -- associated name
        acsSerialPortTableProfile         INTEGER,      -- configured profile
        acsSerialPortTablePinOut          SerialPortPinOut,      -- configure RJ45 pin-out
        acsSerialPortTableComSpeed        SerialPortSpeed,      -- configured speed
        acsSerialPortTableComParity       INTEGER,      -- configured parity
        acsSerialPortTableComDataSize     Integer32,    -- configured data size
        acsSerialPortTableComStopBits     Integer32,      -- configured stop bits
        acsSerialPortTableComFlowControl  INTEGER,      -- configured flow control
        acsSerialPortTableSignalStateDTR  SerialPortSignalState,      -- state of DTR RS-232C signal
        acsSerialPortTableSignalStateDCD  SerialPortSignalState,      -- state of DCD RS-232C signal
        acsSerialPortTableSignalStateRTS  SerialPortSignalState,      -- state of RTS RS-232C signal
        acsSerialPortTableSignalStateCTS  SerialPortSignalState,      -- state of CTS RS-232C signal
        acsSerialPortTableTxBytes         Integer32,    -- number of transmitted bytes
        acsSerialPortTableRxBytes         Integer32,    -- number of received bytes
        acsSerialPortTableFrameError      Integer32,    -- number of detected frame errors
        acsSerialPortTableParityError     Integer32,    -- number of detected parity errors
        acsSerialPortTableBreak           Integer32,    -- number of detected break
        acsSerialPortTableOverrun         Integer32    -- number of detected overrun errors
}

acsSerialPortTableNumber OBJECT-TYPE
        SYNTAX             Integer32 (1..49)
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "A unique index representing an entry in this table.
         It is the number of the serial port. For AUX port,
         the number will be the number of physical serial ports plus 1."
::= { acsSerialPortTableEntry 1 }

acsSerialPortTableDeviceName OBJECT-TYPE
        SYNTAX            DisplayString (SIZE (0..25))
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "The associated device name for the serial port."
::= { acsSerialPortTableEntry 2 }        

acsSerialPortTableStatus OBJECT-TYPE
        SYNTAX INTEGER {
                        disabled(1),
                        idle(2),
                        inUse(3)
             }
        MAX-ACCESS     read-only
        STATUS         current
        DESCRIPTION 
        "The status of the serial port:
         disabled(1) = it was configured as disable.        
         idle(2)     = there is not any session opened in this port.
         inUse(3)    = there is session(s) opened in this port."
::= { acsSerialPortTableEntry 3 }

acsSerialPortTableName    OBJECT-TYPE
        SYNTAX            DisplayString (SIZE (0..25))
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "Name associated with this serial port."
::= { acsSerialPortTableEntry 4 }        

acsSerialPortTableProfile    OBJECT-TYPE
        SYNTAX  INTEGER {
                        casProfile(1),
                        tsProfile(2),
                        dialInProfile(3),
                        powerProfile(4)
                  }
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "Configured profile for this serial port."
::= { acsSerialPortTableEntry 5 }

acsSerialPortTablePinOut    OBJECT-TYPE
        SYNTAX            SerialPortPinOut
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION    
        "RJ45 Pin-out configured for this serial port."
::= { acsSerialPortTableEntry 6 }

acsSerialPortTableComSpeed OBJECT-TYPE
        SYNTAX            SerialPortSpeed
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "Speed configured for this serial port."
::= { acsSerialPortTableEntry 7 }

acsSerialPortTableComParity    OBJECT-TYPE
        SYNTAX  INTEGER {
                        none(1),
                        odd(2),
                        even(3)
                  }
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "Parity configured for this serial port."
::= { acsSerialPortTableEntry 8 }

acsSerialPortTableComDataSize    OBJECT-TYPE
        SYNTAX            Integer32 
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "Data Size configured for this serial port."
::= { acsSerialPortTableEntry 9 }

acsSerialPortTableComStopBits    OBJECT-TYPE
        SYNTAX            Integer32
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "Number of Stop Bits configured for this serial port."
::= { acsSerialPortTableEntry 10 }

acsSerialPortTableComFlowControl        OBJECT-TYPE
        SYNTAX  INTEGER {
                        none(1),
                        hardware(2),
                        software(3)
                  }
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "Flow Control configured for this serial port."
::= { acsSerialPortTableEntry 11 }

acsSerialPortTableSignalStateDTR        OBJECT-TYPE
        SYNTAX            SerialPortSignalState
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "State of the DTR RS-232C signal."
::= { acsSerialPortTableEntry 12 }

acsSerialPortTableSignalStateDCD        OBJECT-TYPE
        SYNTAX            SerialPortSignalState
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "State of the DCD RS-232C signal."
::= { acsSerialPortTableEntry 13 }

acsSerialPortTableSignalStateRTS        OBJECT-TYPE
        SYNTAX            SerialPortSignalState
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "State of the RTS RS-232C signal."
::= { acsSerialPortTableEntry 14 }

acsSerialPortTableSignalStateCTS        OBJECT-TYPE
        SYNTAX            SerialPortSignalState
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "State of the CTS RS-232C signal."
::= { acsSerialPortTableEntry 15 }

acsSerialPortTableTxBytes        OBJECT-TYPE
        SYNTAX            Integer32 
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "The number of transmited bytes by the serial port."
::= { acsSerialPortTableEntry 16 }

acsSerialPortTableRxBytes        OBJECT-TYPE
        SYNTAX            Integer32 
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "The number of received bytes by the serial port."
::= { acsSerialPortTableEntry 17 }

acsSerialPortTableFrameError        OBJECT-TYPE
        SYNTAX            Integer32 
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "The number of frame error detected in the serial port."
::= { acsSerialPortTableEntry 18 }

acsSerialPortTableParityError        OBJECT-TYPE
        SYNTAX            Integer32 
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "The number of parity error detected in the serial port."
::= { acsSerialPortTableEntry 19 }

acsSerialPortTableBreak        OBJECT-TYPE
        SYNTAX            Integer32 
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "The number of break detected in the serial port."
::= { acsSerialPortTableEntry 20 }

acsSerialPortTableOverrun        OBJECT-TYPE
        SYNTAX            Integer32 
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION        
        "The number of overrun error detected in the serial port."
::= { acsSerialPortTableEntry 21 }

--
-- acsPowerMgmt     
-- OBJECT IDENTIFIER ::= { acsManagement 5  }   10418.16.2.5
--
acsPowerMgmtNumSerialPorts OBJECT-TYPE
	  SYNTAX		Integer32
	  MAX-ACCESS	read-only
	  STATUS		current
	  DESCRIPTION	
        "The number of Serial Ports that has PDU connected on the appliance."
::= { acsPowerMgmt 1 }

acsPowerMgmtSerialTable OBJECT-TYPE
	  SYNTAX		SEQUENCE OF AcsPowerMgmtSerialTableEntry
	  MAX-ACCESS	not-accessible
	  STATUS		current
	  DESCRIPTION	
        "Information about each serial port thas has PDU connect."
::= { acsPowerMgmt 2 }

acsPowerMgmtSerialTableEntry	OBJECT-TYPE
        SYNTAX          AcsPowerMgmtSerialTableEntry
        MAX-ACCESS      not-accessible
        STATUS          current
        DESCRIPTION	
        "Information about each serial port thas has PDU connect."
        INDEX           { acsPowerMgmtSerialTableIndex }
::= { acsPowerMgmtSerialTable 1 }

AcsPowerMgmtSerialTableEntry ::= SEQUENCE  {
        acsPowerMgmtSerialTableIndex          InterfaceIndex,   
        acsPowerMgmtSerialTablePortNumber     Integer32,
        acsPowerMgmtSerialTableDeviceName     DisplayString,     
        acsPowerMgmtSerialTableNumberPDUs     Integer32
}

acsPowerMgmtSerialTableIndex	OBJECT-TYPE
        SYNTAX         InterfaceIndex	
        MAX-ACCESS     read-only
        STATUS         current
        DESCRIPTION
        "The index of the register."
::= { acsPowerMgmtSerialTableEntry 1 }

acsPowerMgmtSerialTablePortNumber	OBJECT-TYPE
        SYNTAX         Integer32	
        MAX-ACCESS     read-only
        STATUS         current
        DESCRIPTION
        "The number of the serial port when the PDU is connected."
::= { acsPowerMgmtSerialTableEntry 2 }

acsPowerMgmtSerialTableDeviceName  OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "The device name of this serial port."
::= { acsPowerMgmtSerialTableEntry 3 }

acsPowerMgmtSerialTableNumberPDUs		OBJECT-TYPE
	  SYNTAX          Integer32	
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION
        "Total number of units connected in this serial port."
::= { acsPowerMgmtSerialTableEntry 4 }
	
acsPowerMgmtPDUTable OBJECT-TYPE
        SYNTAX             SEQUENCE OF AcsPowerMgmtPDUTableEntry
        MAX-ACCESS         not-accessible
        STATUS             current
        DESCRIPTION
        "This table contains the list of detected PDUs."
::= { acsPowerMgmt 3 }
 
acsPowerMgmtPDUTableEntry        OBJECT-TYPE
        SYNTAX            AcsPowerMgmtPDUTableEntry
        MAX-ACCESS        not-accessible
        STATUS            current
        DESCRIPTION                
        "each entry has the information about the PDU."
        INDEX                { acsPowerMgmtPDUTablePortNumber, acsPowerMgmtPDUTablePduIndex }
::= { acsPowerMgmtPDUTable 1 }

AcsPowerMgmtPDUTableEntry ::= SEQUENCE  {
        acsPowerMgmtPDUTablePortNumber        InterfaceIndex,  -- number of serial port
        acsPowerMgmtPDUTablePduIndex          InterfaceIndexOrZero,     
        acsPowerMgmtPDUTablePduId             DisplayString,   -- PDU identification
	acsPowerMgmtPDUTablePortName          DisplayString,   -- Serial Port Name
        acsPowerMgmtPDUTableModel             DisplayString,   -- PDU model
        acsPowerMgmtPDUTableVendor            DisplayString,   -- Vendor
        acsPowerMgmtPDUTableFirmwareVersion   DisplayString,   -- Firmware Version
        acsPowerMgmtPDUTableNumberOfOutlets   Integer32, 
        acsPowerMgmtPDUTableCurrentNOS        Integer32,        -- OBSOLETED number of current sensors
        acsPowerMgmtPDUTableCurrent1Value     Integer32,        -- OBSOLETED actual value for current of the sensor 1
        acsPowerMgmtPDUTableCurrent1Max       Integer32,        -- OBSOLETED max value for current of the sensor 1
        acsPowerMgmtPDUTableCurrent2Value     Integer32,        -- OBSOLETED actual value for current of the sensor 2
        acsPowerMgmtPDUTableCurrent2Max       Integer32,        -- OBSOLETED max value for current of the sensor 2
        acsPowerMgmtPDUTableCurrent3Value     Integer32,        -- OBSOLETED actual value for current of the sensor 3
        acsPowerMgmtPDUTableCurrent3Max       Integer32,        -- OBSOLETED max value for current of the sensor 3
        acsPowerMgmtPDUTableTemperatureNOS    Integer32,        -- OBSOLETED number of temperature  sensors
        acsPowerMgmtPDUTableTemperature1Value Integer32,        -- OBSOLETED actual value for Temperature 1
        acsPowerMgmtPDUTableTemperature1Max   Integer32,        -- OBSOLETED max value for Temperature 1
        acsPowerMgmtPDUTableTemperature2Value Integer32,        -- OBSOLETED actual value for Temperaturet 2
        acsPowerMgmtPDUTableTemperature2Max   Integer32,        -- OBSOLETED max value for Temperature 2
        acsPowerMgmtPDUTableTemperature3Value Integer32,        -- OBSOLETED actual value for Temperature 3
        acsPowerMgmtPDUTableTemperature3Max   Integer32,        -- OBSOLETED max value for Temperature 3
        acsPowerMgmtPDUTableHumidityNOS       Integer32,        -- OBSOLETED humidity number of humidity sensors
        acsPowerMgmtPDUTableHumidity1Value    Integer32,        -- OBSOLETED actual value for Humidity of the sensor 1
        acsPowerMgmtPDUTableHumidity1Max      Integer32,        -- OBSOLETED max value for Humidityof the sensor 1
        acsPowerMgmtPDUTableHumidity2Value    Integer32,        -- OBSOLETED actual value for Humidity of the sensor 2
        acsPowerMgmtPDUTableHumidity2Max      Integer32,        -- OBSOLETED max value for Humidity of the sensor 2
        acsPowerMgmtPDUTableHumidity3Value    Integer32,        -- OBSOLETED actual value for Humidity of the sensor 3
        acsPowerMgmtPDUTableHumidity3Max      Integer32,        -- OBSOLETED max value for Humidity of the sensor 3
        acsPowerMgmtPDUTableVoltageNOS        Integer32,        -- OBSOLETED number of voltage sensor
        acsPowerMgmtPDUTableVoltage1Value     Integer32,        -- OBSOLETED actual value for Voltage of the sensor 1
        acsPowerMgmtPDUTableVoltage1Max       Integer32,        -- OBSOLETED max value for Voltage of the sensor 1
        acsPowerMgmtPDUTableVoltage2Value     Integer32,        -- OBSOLETED actual value for Voltage of the sensor 2
        acsPowerMgmtPDUTableVoltage2Max       Integer32,        -- OBSOLETED max value for Voltaget of the sensor 2
        acsPowerMgmtPDUTableVoltage3Value     Integer32,        -- OBSOLETED actual value for Voltage of the sensor 3
        acsPowerMgmtPDUTableVoltage3Max       Integer32,        -- OBSOLETED max value for Voltage of the sensor 3
	acsPowerMgmtPDUTableNumberOfPhases    Integer32,	-- number of phases (single or 3-phases)
	acsPowerMgmtPDUTableNumberOfBanks     Integer32,	-- number of banks
	acsPowerMgmtPDUTableCurrentValue      Integer32,	-- actual value of PDU current sensor 
	acsPowerMgmtPDUTableCurrentMax	      Integer32,	-- max detected value of current sensor
	acsPowerMgmtPDUTableCurrentMin	      Integer32,	-- min detected value of current sensor
	acsPowerMgmtPDUTableCurrentAvg	      Integer32,	-- average value for current sensor
	acsPowerMgmtPDUTableCurrentReset      INTEGER,		-- reset max, min and avg values
	acsPowerMgmtPDUTableVoltageType	      INTEGER,		-- type of PDU voltage 
	acsPowerMgmtPDUTableVoltageValue      Integer32,	-- actual value of PDU voltage
	acsPowerMgmtPDUTableVoltageMax 	      Integer32,	-- max value of voltage sensor
	acsPowerMgmtPDUTableVoltageMin	      Integer32,	-- min value of voltage sensor
	acsPowerMgmtPDUTableVoltageAvg	      Integer32,		-- avg value of voltage sensor
	acsPowerMgmtPDUTableVoltageReset      INTEGER,		-- reset max, min and avg values
	acsPowerMgmtPDUTablePowerType	      INTEGER,		-- type of PDU power consumption
	acsPowerMgmtPDUTablePowerValue	      Integer32,	-- actual value of PDU power consumption
	acsPowerMgmtPDUTablePowerMax	      Integer32,	-- max value
	acsPowerMgmtPDUTablePowerMin	      Integer32,	-- min value
	acsPowerMgmtPDUTablePowerAvg	      Integer32,	-- average value
	acsPowerMgmtPDUTablePowerReset	      INTEGER,		-- reset max, min and avg values
	acsPowerMgmtPDUTablePowerFactorType   INTEGER,		-- type of PDU power factor
	acsPowerMgmtPDUTablePowerFactorValue  Integer32,	-- actual value of PDU power factor
	acsPowerMgmtPDUTablePowerFactorMax    Integer32,	-- max value for power factor
	acsPowerMgmtPDUTablePowerFactorMin    Integer32,	-- min value for power factor
	acsPowerMgmtPDUTablePowerFactorAvg    Integer32,	-- avg value for power factor
	acsPowerMgmtPDUTablePowerFactorReset  INTEGER,		-- reset max, min and avg values
	acsPowerMgmtPDUTableAlarm 	      INTEGER,		-- status of PDU alarm
	acsPowerMgmtPDUTableEnvSensors	      Integer32		-- number of environmental sensors	
}

acsPowerMgmtPDUTablePortNumber OBJECT-TYPE
        SYNTAX            InterfaceIndex
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "Number of serial port when the PDU is connected."
::= { acsPowerMgmtPDUTableEntry 1 }

acsPowerMgmtPDUTablePduIndex OBJECT-TYPE
        SYNTAX            InterfaceIndexOrZero
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "A PDU position in the chain."
::= { acsPowerMgmtPDUTableEntry 2 }

acsPowerMgmtPDUTablePduId  OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "PDU identification."
::= { acsPowerMgmtPDUTableEntry 3 }

acsPowerMgmtPDUTablePortName OBJECT-TYPE
        SYNTAX             DisplayString

        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Name of serial port when the PDU is connected."
::= { acsPowerMgmtPDUTableEntry 4 }

acsPowerMgmtPDUTableModel  OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Model of the PDU."
::= { acsPowerMgmtPDUTableEntry 5 }

acsPowerMgmtPDUTableVendor   OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Vendor of the PDU."
::= { acsPowerMgmtPDUTableEntry 6 }

acsPowerMgmtPDUTableFirmwareVersion        OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Version of the PDU firmware."
::= { acsPowerMgmtPDUTableEntry 7 }

acsPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Number of outlets of the PDU."
::= { acsPowerMgmtPDUTableEntry 8 }

acsPowerMgmtPDUTableCurrentNOS OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Number of current sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 9 }

acsPowerMgmtPDUTableCurrent1Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Current of the sensor 1 in this PDU unit in AMP.
         The value of this object is the actual current in 
         AMP * 10. You need to translate the readed value
         (Ex. : value is 5, the current is 0.5 AMP.)" 
::= { acsPowerMgmtPDUTableEntry 10 }

acsPowerMgmtPDUTableCurrent1Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum current of the sensor 1 in this PDU unit in AMP.
         When the PDU does not have support for maximum value,
         the value will be 0.
         The value of this object is the actual current in 
         AMP * 10. You need to translate the readed value
         (Ex. : value is 5, the current is 0.5 AMP.)
         Clear this value, set it with Zero value." 
::= { acsPowerMgmtPDUTableEntry 11 }

acsPowerMgmtPDUTableCurrent2Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Current of the sensor 2 in this PDU unit in AMP.
         The value of this object is the actual current in 
         AMP * 10. You need to translate the readed value
         (Ex. : value is 5, the current is 0.5 AMP.)" 
::= { acsPowerMgmtPDUTableEntry 12 }

acsPowerMgmtPDUTableCurrent2Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum current of the sensor 2 in this PDU unit in AMP.
          When the PDU does not have support for maximum value,
         the value will be 0.
         The value of this object is the actual current in 
         AMP * 10. You need to translate the readed value
         (Ex. : value is 5, the current is 0.5 AMP.)
         Clear this value, set it with Zero value." 
::= { acsPowerMgmtPDUTableEntry 13}

acsPowerMgmtPDUTableCurrent3Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Current of the sensor 3 in this PDU unit in AMP.
         The value of this object is the actual current in 
         AMP * 10. You need to translate the readed value
        (Ex. : value is 5, the current is 0.5 AMP.)" 
::= { acsPowerMgmtPDUTableEntry 14 }

acsPowerMgmtPDUTableCurrent3Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
         "Maximum current of the sensor 3 in this PDU unit in AMP.
         When the PDU does not have support for maximum value,
         the value will be 0.
         The value of this object is the actual current in 
         AMP * 10. You need to translate the readed value
         (Ex. : value is 5, the current is 0.5 AMP.)
         Clear this value, set it with Zero value." 
::= { acsPowerMgmtPDUTableEntry 15 }

acsPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Number of temperature sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 16 }

acsPowerMgmtPDUTableTemperature1Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Temperature of this PM unit in Celsius degrees.
         The value of this object is the actual temperature in 
         degrees C * 10. You need to translate the readed value
        (Ex. : value is 240, the temperature is 24 Celsius.) 
         If the temperature measurement is not installed this 
         value will be 0.
        Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)." 
::= { acsPowerMgmtPDUTableEntry 17 }

acsPowerMgmtPDUTableTemperature1Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum temperature detected in this PM unit in Celsius degrees.
        The value will be Zero when the PDU does not have support for maximum value.
         The value of this object is the actual temperature in 
         degrees C * 10. You need to translate the readed value
        (Ex. : value is 240, the temperature is 24 Celsius.) 
         If the temperature measurement is not installed this 
         value will be 0.
         Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
        Set with Zero value to clear the max. temperature." 
::= { acsPowerMgmtPDUTableEntry 18 }

acsPowerMgmtPDUTableTemperature2Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Temperature of this PM unit in Celsius degrees.
         The value of this object is the actual temperature in 
         degrees C * 10. You need to translate the readed value
         (Ex. : value is 240, the temperature is 24 Celsius.) 
         If the temperature measurement is not installed this 
         value will be 0.
          Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)." 
::= { acsPowerMgmtPDUTableEntry 19 }

acsPowerMgmtPDUTableTemperature2Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum temperature detected in this PM unit in Celsius degrees.
         The value will be Zero when the PDU does not have support for maximum value.
         The value of this object is the actual temperature in 
         degrees C * 10. You need to translate the readed value
         (Ex. : value is 240, the temperature is 24 Celsius.) 
         If the temperature measurement is not installed this 
         value will be 0.
         Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
         Set with Zero value to clear the max. temperature." 
::= { acsPowerMgmtPDUTableEntry 20 }

acsPowerMgmtPDUTableTemperature3Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Temperature of this PM unit in Celsius degrees.
        The value of this object is the actual temperature in 
        degrees C * 10. You need to translate the readed value
        (Ex. : value is 240, the temperature is 24 Celsius.) 
        If the temperature measurement is not installed this 
        value will be 0.
        Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)." 
::= { acsPowerMgmtPDUTableEntry 21 }

acsPowerMgmtPDUTableTemperature3Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum temperature detected in this PM unit in Celsius degrees.
        The value will be Zero when the PDU does not have support for maximum value.
         The value of this object is the actual temperature in 
         degrees C * 10. You need to translate the readed value
         (Ex. : value is 240, the temperature is 24 Celsius.) 
         If the temperature measurement is not installed this 
         value will be 0.
         Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
         Set with Zero value to clear the max. temperature." 
::= { acsPowerMgmtPDUTableEntry 22 }

acsPowerMgmtPDUTableHumidityNOS OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Number of humidity sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 23 }

acsPowerMgmtPDUTableHumidity1Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Humidity of this PM unit .
         If the humidity measurement is not installed this 
         value will be 0." 
::= {  acsPowerMgmtPDUTableEntry 24 }

acsPowerMgmtPDUTableHumidity1Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum humidity detected in this PM unit.
         If the humidity measurement  is not installed  or the PDU does not have support for maximum value this 
         value will be 0.
         Set with Zero value to clear the max. temperature." 
::= {  acsPowerMgmtPDUTableEntry 25 }

acsPowerMgmtPDUTableHumidity2Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Humidity of this PM unit .
         If the humidity measurement is not installed this 
         value will be 0." 
::= {  acsPowerMgmtPDUTableEntry 26 }

acsPowerMgmtPDUTableHumidity2Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum humidity detected in this PM unit.
         If the humidity measurement  is not installed  or the PDU does not have support for maximum value this 
         value will be 0.
         Set with Zero value to clear the max. temperature." 
::= {  acsPowerMgmtPDUTableEntry 27 }

acsPowerMgmtPDUTableHumidity3Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Humidity of this PM unit .
         If the humidity measurement is not installed this 
         value will be 0." 
::= {  acsPowerMgmtPDUTableEntry 28 }

acsPowerMgmtPDUTableHumidity3Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum humidity detected in this PM unit.
         If the humidity measurement  is not installed  or the PDU does not have support for maximum value this 
         value will be 0.
         Set with Zero value to clear the max. temperature." 
::= {  acsPowerMgmtPDUTableEntry 29 }

acsPowerMgmtPDUTableVoltageNOS OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Number of voltage sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 30 }

acsPowerMgmtPDUTableVoltage1Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Voltage of this sensor in this PDU unit." 
::= { acsPowerMgmtPDUTableEntry 31 }

acsPowerMgmtPDUTableVoltage1Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum voltage of this sensor in this PDU unit.
         Set with Zero value to clear the maximum voltage." 
::= { acsPowerMgmtPDUTableEntry 32 }

acsPowerMgmtPDUTableVoltage2Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Voltage of this sensor in this PDU unit." 
::= { acsPowerMgmtPDUTableEntry 33 }

acsPowerMgmtPDUTableVoltage2Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum voltage of this sensor in this PDU unit.
         Set with Zero value to clear the maximum voltage." 
::= { acsPowerMgmtPDUTableEntry 34 }

acsPowerMgmtPDUTableVoltage3Value OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             obsolete
        DESCRIPTION
        "Voltage of this sensor in this PDU unit." 
::= { acsPowerMgmtPDUTableEntry 35 }

acsPowerMgmtPDUTableVoltage3Max OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-write
        STATUS             obsolete
        DESCRIPTION
        "Maximum voltage of this sensor in this PDU unit.
         Set with Zero value to clear the maximum voltage." 
::= { acsPowerMgmtPDUTableEntry 36 }

acsPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE
        SYNTAX       INTEGER {
			single-phase (0),
			three-phase (3)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Number of phases of this PDU unit."
::= { acsPowerMgmtPDUTableEntry 37 }

acsPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE
        SYNTAX          Integer32
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Number of banks of this PDU unit."
::= { acsPowerMgmtPDUTableEntry 38 }

acsPowerMgmtPDUTableCurrentValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of current sensor in this PDU.( A x 10 )" 
::= { acsPowerMgmtPDUTableEntry 39 }

acsPowerMgmtPDUTableCurrentMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of current sensor in this PDU.( A x 10 )" 
::= { acsPowerMgmtPDUTableEntry 40 }

acsPowerMgmtPDUTableCurrentMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of current sensor in this PDU.( A x 10 )" 
::= { acsPowerMgmtPDUTableEntry 41 }

acsPowerMgmtPDUTableCurrentAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for current sensor in this PDU.( A x 10 )" 
::= { acsPowerMgmtPDUTableEntry 42 }

acsPowerMgmtPDUTableCurrentReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of current."
::= { acsPowerMgmtPDUTableEntry 43 }

acsPowerMgmtPDUTableVoltageType OBJECT-TYPE
        SYNTAX       INTEGER {
			none-sensor (0),
			estimated (1),
			read (2)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Type of voltage values."
::= { acsPowerMgmtPDUTableEntry 44 }

acsPowerMgmtPDUTableVoltageValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of voltage sensor in this PDU unit.( V )" 
::= { acsPowerMgmtPDUTableEntry 45 }

acsPowerMgmtPDUTableVoltageMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of voltage sensor in this PDU unit.( V )" 
::= { acsPowerMgmtPDUTableEntry 46 }

acsPowerMgmtPDUTableVoltageMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of voltage sensor in this PDU unit.( V )" 
::= { acsPowerMgmtPDUTableEntry 47 }

acsPowerMgmtPDUTableVoltageAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for voltage sensor in this PDU unit.( V )" 
::= { acsPowerMgmtPDUTableEntry 48 }

acsPowerMgmtPDUTableVoltageReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of voltage."
::= { acsPowerMgmtPDUTableEntry 49 }

acsPowerMgmtPDUTablePowerType OBJECT-TYPE
        SYNTAX       INTEGER {
			none-sensor (0),
			estimated (1),
			read (2)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Type of power consumption values.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 50 }

acsPowerMgmtPDUTablePowerValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of power consumption in this PDU unit.( W x 10 )" 
::= { acsPowerMgmtPDUTableEntry 51 }

acsPowerMgmtPDUTablePowerMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of power consumption in this PDU unit.( W x 10 )" 
::= { acsPowerMgmtPDUTableEntry 52 }

acsPowerMgmtPDUTablePowerMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of power consumption in this PDU unit.( W x 10 )" 
::= { acsPowerMgmtPDUTableEntry 53 }

acsPowerMgmtPDUTablePowerAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for power consumption in this PDU unit.( W x 10 )" 
::= { acsPowerMgmtPDUTableEntry 54 }

acsPowerMgmtPDUTablePowerReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of power consumption."
::= { acsPowerMgmtPDUTableEntry 55 }

acsPowerMgmtPDUTablePowerFactorType OBJECT-TYPE
        SYNTAX       INTEGER {
			none-sensor (0),
			estimated (1),
			read (2)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Type of power factor values."
::= { acsPowerMgmtPDUTableEntry 56 }

acsPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of power factor in this PDU unit.( PF x 100 )" 
::= { acsPowerMgmtPDUTableEntry 57 }

acsPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of power factor in this PDU unit.( PF x 100 )" 
::= { acsPowerMgmtPDUTableEntry 58 }

acsPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of power factor in this PDU unit.( PF x 100 )" 
::= { acsPowerMgmtPDUTableEntry 59 }

acsPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for power factor in this PDU unit.( PF x 100 )" 
::= { acsPowerMgmtPDUTableEntry 60 }

acsPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of power factor."
::= { acsPowerMgmtPDUTableEntry 61 }

acsPowerMgmtPDUTableAlarm OBJECT-TYPE
        SYNTAX       INTEGER {
			normal (1),
			blow-fuse (2),
			hw-ocp (3),
			high-critical (4),
			high-warning (5),
			low-warning (6),
			low-critical (7)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Show the PDU alarm status."
::= { acsPowerMgmtPDUTableEntry 62 }

acsPowerMgmtPDUTableEnvSensors OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Number of environmental sensor in this PDU." 
::= { acsPowerMgmtPDUTableEntry 63 }

	
acsPowerMgmtTotalNumberOfOutlets OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Number of outlets managed by the appliance."
::= { acsPowerMgmt 4 }

acsPowerMgmtOutletsTable OBJECT-TYPE
        SYNTAX             SEQUENCE OF AcsPowerMgmtOutletsTableEntry
        MAX-ACCESS         not-accessible
        STATUS             current
        DESCRIPTION
        "This table contains the information about outlets."
::= { acsPowerMgmt 5 }
 
acsPowerMgmtOutletsTableEntry  OBJECT-TYPE
        SYNTAX            AcsPowerMgmtOutletsTableEntry
        MAX-ACCESS        not-accessible
        STATUS            current
        DESCRIPTION                
        "each entry has the information about the outlet."
        INDEX             { acsPowerMgmtOutletsTablePortNumber,
                            acsPowerMgmtOutletsTablePduNumber,
                            acsPowerMgmtOutletsTableNumber }
::= { acsPowerMgmtOutletsTable 1 }

AcsPowerMgmtOutletsTableEntry ::= SEQUENCE  {
        acsPowerMgmtOutletsTablePortNumber   InterfaceIndex, -- serial port #
        acsPowerMgmtOutletsTablePduNumber    InterfaceIndex,     
        acsPowerMgmtOutletsTableNumber       InterfaceIndex, -- outlet number in PDU
        acsPowerMgmtOutletsTableName         DisplayString,  -- outlet name
        acsPowerMgmtOutletsTableStatus       INTEGER,        -- outlet status
        acsPowerMgmtOutletsTablePowerControl INTEGER,        -- manage the outlet
        acsPowerMgmtOutletsTablePortName     DisplayString,  -- serial port name
        acsPowerMgmtOutletsTablePduId        DisplayString  -- PDU ID
}

acsPowerMgmtOutletsTablePortNumber OBJECT-TYPE
        SYNTAX             InterfaceIndex
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Serial Port number."
::= { acsPowerMgmtOutletsTableEntry 1 }

acsPowerMgmtOutletsTablePduNumber OBJECT-TYPE
        SYNTAX             InterfaceIndex
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Index."
::= { acsPowerMgmtOutletsTableEntry 2 }

acsPowerMgmtOutletsTableNumber OBJECT-TYPE
        SYNTAX             InterfaceIndex
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Number of the outlet in the PDU."
::= { acsPowerMgmtOutletsTableEntry 3 }

acsPowerMgmtOutletsTableName OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Name of the outlet." 
::= { acsPowerMgmtOutletsTableEntry 4 }

acsPowerMgmtOutletsTableStatus OBJECT-TYPE
        SYNTAX        INTEGER {
                off(1),
                on(2)
        }
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Status of the outlet."
::= { acsPowerMgmtOutletsTableEntry 5 }

acsPowerMgmtOutletsTablePowerControl OBJECT-TYPE
        SYNTAX INTEGER {
                noAction(1),
                powerOn(2),
                powerOff(3),
                powerCycle(4),
                powerLock(5),
                powerUnlock(6)
        }
        MAX-ACCESS         read-write
        STATUS             current
        DESCRIPTION 
        "A set value of power*(2-6) will send command to PDU.
         noAction(1) = always returned in a GET. Does nothing if SET.
         powerOn(2)  = when SET the power On command is sent to PDU.
         powerOff(3) = when SET the power Off command is sent to PDU.
         powerCycle(4)=when SET the power cycle command is sent to PDU.
         powerLock(5)= when SET the power lock command is sent to PDU.
         powerUnlock(6)=when SET the power unlock command is sent to PDU.
        The powerLock and powerUnlock are valid only for Cyclades-PM PDUs"
::= { acsPowerMgmtOutletsTableEntry 6 }

acsPowerMgmtOutletsTablePortName OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Serial Port Name where the PDU is connected."
::= { acsPowerMgmtOutletsTableEntry 7 }

acsPowerMgmtOutletsTablePduId        OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "PDU identification."
::= { acsPowerMgmtOutletsTableEntry 8 }

acsPowerMgmtNumberOfOutletGroup OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Number of configured group of outlets."
::= { acsPowerMgmt 6 }

acsPowerMgmtGroupTable OBJECT-TYPE
        SYNTAX             SEQUENCE OF AcsPowerMgmtGroupTableEntry
        MAX-ACCESS         not-accessible
        STATUS             current
        DESCRIPTION
        "This table contains the information about group of outlets."
::= { acsPowerMgmt 7 }
 
acsPowerMgmtGroupTableEntry  OBJECT-TYPE
        SYNTAX            AcsPowerMgmtGroupTableEntry
        MAX-ACCESS        not-accessible
        STATUS            current
        DESCRIPTION                
        "each entry has the information about group of outlets."
        INDEX             { acsPowerMgmtGroupTableIndex }
::= { acsPowerMgmtGroupTable 1 }

AcsPowerMgmtGroupTableEntry ::= SEQUENCE  {
        acsPowerMgmtGroupTableIndex           InterfaceIndexOrZero,      
        acsPowerMgmtGroupTableName            DisplayString, -- group name
        acsPowerMgmtGroupTableStatus          INTEGER,            -- group status
        acsPowerMgmtGroupTablePowerControl    INTEGER    -- manage the group        
}

acsPowerMgmtGroupTableIndex OBJECT-TYPE
        SYNTAX             InterfaceIndexOrZero
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Index of the group."
::= { acsPowerMgmtGroupTableEntry 1 }

acsPowerMgmtGroupTableName OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Name of the group of outlets." 
::= { acsPowerMgmtGroupTableEntry 2 }

acsPowerMgmtGroupTableStatus OBJECT-TYPE
        SYNTAX INTEGER {
                off(1),
                on(2)
                }
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Status of the group of outlet."
::= { acsPowerMgmtGroupTableEntry 3 }

acsPowerMgmtGroupTablePowerControl OBJECT-TYPE
        SYNTAX INTEGER {
                noAction(1),
                powerOn(2),
                powerOff(3),
                powerCycle(4)
        }
        MAX-ACCESS         read-write
        STATUS             current
        DESCRIPTION 
        "A set value of power*(2-6) will send command to PDU.
         noAction(1) = always returned in a GET. Does nothing if SET.
         powerOn(2)  = when SET the power On command is sent to PDU.
         powerOff(3) = when SET the power Off command is sent to PDU.
         powerCycle(4)=when SET the power cycle command is sent to PDU."
::= { acsPowerMgmtGroupTableEntry 4 }

acsPowerMgmtPhasesTable OBJECT-TYPE
        SYNTAX             SEQUENCE OF AcsPowerMgmtPhasesTableEntry
        MAX-ACCESS         not-accessible
        STATUS             current
        DESCRIPTION
        "This table contains data monitoring of each detected phase."
::= { acsPowerMgmt 8 }
 
acsPowerMgmtPhasesTableEntry        OBJECT-TYPE
        SYNTAX            AcsPowerMgmtPhasesTableEntry
        MAX-ACCESS        not-accessible
        STATUS            current
        DESCRIPTION                
        "each entry has the data monitoring about phases."
        INDEX  { acsPowerMgmtPhasesTablePortNumber, acsPowerMgmtPhasesTablePduIndex, acsPowerMgmtPhasesTablePhaseIndex }
::= { acsPowerMgmtPhasesTable 1 }

AcsPowerMgmtPhasesTableEntry ::= SEQUENCE  {
        acsPowerMgmtPhasesTablePortNumber        InterfaceIndex,  -- number of serial port
        acsPowerMgmtPhasesTablePduIndex          InterfaceIndexOrZero, -- number of PDU
        acsPowerMgmtPhasesTablePhaseIndex        InterfaceIndexOrZero, -- phase index
	acsPowerMgmtPhasesTablePhaseName         DisplayString,   -- Phase Name
        acsPowerMgmtPhasesTablePduId             DisplayString,   -- PDU identification
	acsPowerMgmtPhasesTablePortName          DisplayString,   -- Serial Port Name
	acsPowerMgmtPhasesTableCurrentValue      Integer32,	-- actual value of Phase current sensor 
	acsPowerMgmtPhasesTableCurrentMax	 Integer32,	-- max detected value of current sensor
	acsPowerMgmtPhasesTableCurrentMin	 Integer32,	-- min detected value of current sensor
	acsPowerMgmtPhasesTableCurrentAvg	 Integer32,	-- average value for current sensor
	acsPowerMgmtPhasesTableCurrentReset      INTEGER,	-- reset max, min and avg values
	acsPowerMgmtPhasesTableVoltageType	 INTEGER,	-- type of phase voltage 
	acsPowerMgmtPhasesTableVoltageValue      Integer32,	-- actual value of phase voltage
	acsPowerMgmtPhasesTableVoltageMax 	 Integer32,	-- max value of voltage sensor
	acsPowerMgmtPhasesTableVoltageMin	 Integer32,	-- min value of voltage sensor
	acsPowerMgmtPhasesTableVoltageAvg	 Integer32,	-- avg value of voltage sensor
	acsPowerMgmtPhasesTableVoltageReset      INTEGER,	-- reset max, min and avg values
	acsPowerMgmtPhasesTablePowerType	 INTEGER,	-- type of phase power consumption
	acsPowerMgmtPhasesTablePowerValue	 Integer32,	-- actual value of phase power consumption
	acsPowerMgmtPhasesTablePowerMax	         Integer32,	-- max value
	acsPowerMgmtPhasesTablePowerMin	         Integer32,	-- min value
	acsPowerMgmtPhasesTablePowerAvg	         Integer32,	-- average value
	acsPowerMgmtPhasesTablePowerReset	 INTEGER,	-- reset max, min and avg values
	acsPowerMgmtPhasesTablePowerFactorType   INTEGER,	-- type of phase power factor
	acsPowerMgmtPhasesTablePowerFactorValue  Integer32,	-- actual value of phase power factor
	acsPowerMgmtPhasesTablePowerFactorMax    Integer32,	-- max value for power factor
	acsPowerMgmtPhasesTablePowerFactorMin    Integer32,	-- min value for power factor
	acsPowerMgmtPhasesTablePowerFactorAvg    Integer32,	-- avg value for power factor
	acsPowerMgmtPhasesTablePowerFactorReset  INTEGER,	-- reset max, min and avg values
	acsPowerMgmtPhasesTableAlarm 	         INTEGER	-- phase alarm status
}

acsPowerMgmtPhasesTablePortNumber OBJECT-TYPE
        SYNTAX            InterfaceIndex
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "Number of serial port when the PDU is connected."
::= { acsPowerMgmtPhasesTableEntry 1 }

acsPowerMgmtPhasesTablePduIndex OBJECT-TYPE
        SYNTAX            InterfaceIndexOrZero
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "A PDU position in the chain."
::= { acsPowerMgmtPhasesTableEntry 2 }

acsPowerMgmtPhasesTablePhaseIndex OBJECT-TYPE
        SYNTAX            InterfaceIndexOrZero
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "phase index in the PDU."
::= { acsPowerMgmtPhasesTableEntry 3 }

acsPowerMgmtPhasesTablePhaseName OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "phase name in the PDU."
::= { acsPowerMgmtPhasesTableEntry 4 }

acsPowerMgmtPhasesTablePduId  OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "PDU identification."
::= { acsPowerMgmtPhasesTableEntry 5 }

acsPowerMgmtPhasesTablePortName OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Name of serial port when the PDU is connected."
::= { acsPowerMgmtPhasesTableEntry 6 }

acsPowerMgmtPhasesTableCurrentValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of current sensor in this phase.( A x 10 )" 
::= { acsPowerMgmtPhasesTableEntry 7 }

acsPowerMgmtPhasesTableCurrentMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of current sensor in this phase.( A x 10 )" 
::= { acsPowerMgmtPhasesTableEntry 8 }

acsPowerMgmtPhasesTableCurrentMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of current sensor in this phase.( A x 10 )" 
::= { acsPowerMgmtPhasesTableEntry 9 }

acsPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for current sensor in this phase.( A x 10 )" 
::= { acsPowerMgmtPhasesTableEntry 10 }

acsPowerMgmtPhasesTableCurrentReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of current."
::= { acsPowerMgmtPhasesTableEntry 11 }

acsPowerMgmtPhasesTableVoltageType OBJECT-TYPE
        SYNTAX       INTEGER {
			none-sensor (0),
			estimated (1),
			read (2)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Type of voltage values."
::= { acsPowerMgmtPhasesTableEntry 12 }

acsPowerMgmtPhasesTableVoltageValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of voltage sensor in this phase.( V )" 
::= { acsPowerMgmtPhasesTableEntry 13 }

acsPowerMgmtPhasesTableVoltageMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of voltage sensor in this phase.( V )" 
::= { acsPowerMgmtPhasesTableEntry 14 }

acsPowerMgmtPhasesTableVoltageMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of voltage sensor in this phase.( V )" 
::= { acsPowerMgmtPhasesTableEntry 15 }

acsPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for voltage sensor in this phase.( V )" 
::= { acsPowerMgmtPhasesTableEntry 16 }

acsPowerMgmtPhasesTableVoltageReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of voltage."
::= { acsPowerMgmtPhasesTableEntry 17 }

acsPowerMgmtPhasesTablePowerType OBJECT-TYPE
        SYNTAX       INTEGER {
			none-sensor (0),
			estimated (1),
			read (2)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Type of power consumption values."
::= { acsPowerMgmtPhasesTableEntry 18 }

acsPowerMgmtPhasesTablePowerValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of power consumption in this phase.( W x 10 )" 
::= { acsPowerMgmtPhasesTableEntry 19 }

acsPowerMgmtPhasesTablePowerMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of power consumption in this phase.( W x 10 )" 
::= { acsPowerMgmtPhasesTableEntry 20 }

acsPowerMgmtPhasesTablePowerMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of power consumption in this phase.( W x 10 )" 
::= { acsPowerMgmtPhasesTableEntry 21 }

acsPowerMgmtPhasesTablePowerAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for power consumption in this phase.( W x 10 )" 
::= { acsPowerMgmtPhasesTableEntry 22 }

acsPowerMgmtPhasesTablePowerReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of power consumption."
::= { acsPowerMgmtPhasesTableEntry 23 }

acsPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE
        SYNTAX       INTEGER {
			none-sensor (0),
			estimated (1),
			read (2)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Type of power factor values."
::= { acsPowerMgmtPhasesTableEntry 24 }

acsPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of power factor in this phase.( PF x 100 )" 
::= { acsPowerMgmtPhasesTableEntry 25 }

acsPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of power factor in this phase.( PF x 100 )" 
::= { acsPowerMgmtPhasesTableEntry 26 }

acsPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of power factor in this phase.( PF x 100 )" 
::= { acsPowerMgmtPhasesTableEntry 27 }

acsPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for power factor in this phase.( PF x 100 )" 
::= { acsPowerMgmtPhasesTableEntry 28 }

acsPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of power factor."
::= { acsPowerMgmtPhasesTableEntry 29 }

acsPowerMgmtPhasesTableAlarm OBJECT-TYPE
        SYNTAX       INTEGER {
			normal (1),
			blow-fuse (2),
			hw-ocp (3),
			high-critical (4),
			high-warning (5),
			low-warning (6),
			low-critical (7)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Show the phase alarm status."
::= { acsPowerMgmtPhasesTableEntry 30 }

acsPowerMgmtBanksTable OBJECT-TYPE
        SYNTAX             SEQUENCE OF AcsPowerMgmtBanksTableEntry
        MAX-ACCESS         not-accessible
        STATUS             current
        DESCRIPTION
        "This table contains data monitoring of each detected bank."
::= { acsPowerMgmt 9 }
 
acsPowerMgmtBanksTableEntry        OBJECT-TYPE
        SYNTAX            AcsPowerMgmtBanksTableEntry
        MAX-ACCESS        not-accessible
        STATUS            current
        DESCRIPTION                
        "each entry has the data monitoring about bank."
        INDEX  { acsPowerMgmtBanksTablePortNumber, acsPowerMgmtBanksTablePduIndex, acsPowerMgmtBanksTableBankIndex }
::= { acsPowerMgmtBanksTable 1 }

AcsPowerMgmtBanksTableEntry ::= SEQUENCE  {
        acsPowerMgmtBanksTablePortNumber        InterfaceIndex,  -- number of serial port
        acsPowerMgmtBanksTablePduIndex          InterfaceIndexOrZero, -- number of PDU
        acsPowerMgmtBanksTableBankIndex         InterfaceIndexOrZero, -- bank index
	acsPowerMgmtBanksTableBankName          DisplayString,   -- Bank Name
        acsPowerMgmtBanksTablePduId             DisplayString,   -- PDU identification
	acsPowerMgmtBanksTablePortName          DisplayString,   -- Serial Port Name
	acsPowerMgmtBanksTableCurrentValue      Integer32,	-- actual value of bank current sensor 
	acsPowerMgmtBanksTableCurrentMax	Integer32,	-- max detected value of current sensor
	acsPowerMgmtBanksTableCurrentMin	Integer32,	-- min detected value of current sensor
	acsPowerMgmtBanksTableCurrentAvg	Integer32,	-- average value for current sensor
	acsPowerMgmtBanksTableCurrentReset      INTEGER,	-- reset max, min and avg values
	acsPowerMgmtBanksTableVoltageType	INTEGER,	-- type of bank voltage 
	acsPowerMgmtBanksTableVoltageValue      Integer32,	-- actual value of bank voltage
	acsPowerMgmtBanksTableVoltageMax 	Integer32,	-- max value of voltage sensor
	acsPowerMgmtBanksTableVoltageMin	Integer32,	-- min value of voltage sensor
	acsPowerMgmtBanksTableVoltageAvg	Integer32,	-- avg value of voltage sensor
	acsPowerMgmtBanksTableVoltageReset      INTEGER,	-- reset max, min and avg values
	acsPowerMgmtBanksTablePowerType	 	INTEGER,	-- type of bank power consumption
	acsPowerMgmtBanksTablePowerValue	Integer32,	-- actual value of bank power consumption
	acsPowerMgmtBanksTablePowerMax	        Integer32,	-- max value
	acsPowerMgmtBanksTablePowerMin	        Integer32,	-- min value
	acsPowerMgmtBanksTablePowerAvg	        Integer32,	-- average value
	acsPowerMgmtBanksTablePowerReset	INTEGER,	-- reset max, min and avg values
	acsPowerMgmtBanksTablePowerFactorType   INTEGER,	-- type of bank power factor
	acsPowerMgmtBanksTablePowerFactorValue  Integer32,	-- actual value of bank power factor
	acsPowerMgmtBanksTablePowerFactorMax    Integer32,	-- max value for power factor
	acsPowerMgmtBanksTablePowerFactorMin    Integer32,	-- min value for power factor
	acsPowerMgmtBanksTablePowerFactorAvg    Integer32,	-- avg value for power factor
	acsPowerMgmtBanksTablePowerFactorReset  INTEGER,	-- reset max, min and avg values
	acsPowerMgmtBanksTableAlarm 	        INTEGER	-- status of bank alarm
}

acsPowerMgmtBanksTablePortNumber OBJECT-TYPE
        SYNTAX            InterfaceIndex
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "Number of serial port when the PDU is connected."
::= { acsPowerMgmtBanksTableEntry 1 }

acsPowerMgmtBanksTablePduIndex OBJECT-TYPE
        SYNTAX            InterfaceIndexOrZero
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "A PDU position in the chain."
::= { acsPowerMgmtBanksTableEntry 2 }

acsPowerMgmtBanksTableBankIndex OBJECT-TYPE
        SYNTAX            InterfaceIndexOrZero
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "Bank index in the PDU."
::= { acsPowerMgmtBanksTableEntry 3 }

acsPowerMgmtBanksTableBankName OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Bank name in the PDU."
::= { acsPowerMgmtBanksTableEntry 4 }

acsPowerMgmtBanksTablePduId  OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "PDU identification."
::= { acsPowerMgmtBanksTableEntry 5 }

acsPowerMgmtBanksTablePortName OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Name of serial port when the PDU is connected."
::= { acsPowerMgmtBanksTableEntry 6 }

acsPowerMgmtBanksTableCurrentValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of current sensor in this bank.( A x 10 )" 
::= { acsPowerMgmtBanksTableEntry 7 }

acsPowerMgmtBanksTableCurrentMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of current sensor in this bank.( A x 10 )" 
::= { acsPowerMgmtBanksTableEntry 8 }

acsPowerMgmtBanksTableCurrentMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of current sensor in this bank.( A x 10 )" 
::= { acsPowerMgmtBanksTableEntry 9 }

acsPowerMgmtBanksTableCurrentAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for current sensor in this bank.( A x 10 )" 
::= { acsPowerMgmtBanksTableEntry 10 }

acsPowerMgmtBanksTableCurrentReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of current."
::= { acsPowerMgmtBanksTableEntry 11 }

acsPowerMgmtBanksTableVoltageType OBJECT-TYPE
        SYNTAX       INTEGER {
			none-sensor (0),
			estimated (1),
			read (2)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Type of voltage values."
::= { acsPowerMgmtBanksTableEntry 12 }

acsPowerMgmtBanksTableVoltageValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of voltage sensor in this bank.( V )" 
::= { acsPowerMgmtBanksTableEntry 13 }

acsPowerMgmtBanksTableVoltageMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of voltage sensor in this bank.( V )" 
::= { acsPowerMgmtBanksTableEntry 14 }

acsPowerMgmtBanksTableVoltageMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of voltage sensor in this bank.( V )" 
::= { acsPowerMgmtBanksTableEntry 15 }

acsPowerMgmtBanksTableVoltageAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for voltage sensor in this bank.( V )" 
::= { acsPowerMgmtBanksTableEntry 16 }

acsPowerMgmtBanksTableVoltageReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of voltage."
::= { acsPowerMgmtBanksTableEntry 17 }

acsPowerMgmtBanksTablePowerType OBJECT-TYPE
        SYNTAX       INTEGER {
			none-sensor (0),
			estimated (1),
			read (2)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Type of power consumption values."
::= { acsPowerMgmtBanksTableEntry 18 }

acsPowerMgmtBanksTablePowerValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of power consumption in this bank.( W x 10 )" 
::= { acsPowerMgmtBanksTableEntry 19 }

acsPowerMgmtBanksTablePowerMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of power consumption in this bank.( W x 10 )" 
::= { acsPowerMgmtBanksTableEntry 20 }

acsPowerMgmtBanksTablePowerMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of power consumption in this bank.( W x 10 )" 
::= { acsPowerMgmtBanksTableEntry 21 }

acsPowerMgmtBanksTablePowerAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for power consumption in this bank.( W x 10 )" 
::= { acsPowerMgmtBanksTableEntry 22 }

acsPowerMgmtBanksTablePowerReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of power consumption."
::= { acsPowerMgmtBanksTableEntry 23 }

acsPowerMgmtBanksTablePowerFactorType OBJECT-TYPE
        SYNTAX       INTEGER {
			none-sensor (0),
			estimated (1),
			read (2)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Type of power factor values."
::= { acsPowerMgmtBanksTableEntry 24 }

acsPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of power factor in this bank.( PF x 100 )" 
::= { acsPowerMgmtBanksTableEntry 25 }

acsPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of power factor in this bank.( PF x 100 )" 
::= { acsPowerMgmtBanksTableEntry 26 }

acsPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of power factor in this bank.( PF x 100 )" 
::= { acsPowerMgmtBanksTableEntry 27 }

acsPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for power factor in this bank.( PF x 100 )" 
::= { acsPowerMgmtBanksTableEntry 28 }

acsPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE
        SYNTAX       INTEGER {
			no-action (1),
			reset (2)
                    }
        MAX-ACCESS      read-write
        STATUS          current
        DESCRIPTION     "Reset max, min and avg values of power factor."
::= { acsPowerMgmtBanksTableEntry 29 }

acsPowerMgmtBanksTableAlarm OBJECT-TYPE
        SYNTAX       INTEGER {
			normal (1),
			blow-fuse (2),
			hw-ocp (3),
			high-critical (4),
			high-warning (5),
			low-warning (6),
			low-critical (7)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Show the bank alarm status."
::= { acsPowerMgmtBanksTableEntry 30 }

acsPowerMgmtEnvMonTable OBJECT-TYPE
        SYNTAX             SEQUENCE OF AcsPowerMgmtEnvMonTableEntry
        MAX-ACCESS         not-accessible
        STATUS             current
        DESCRIPTION
        "This table contains data monitoring of each detected environmental sensor."
::= { acsPowerMgmt 10 }
 
acsPowerMgmtEnvMonTableEntry        OBJECT-TYPE
        SYNTAX            AcsPowerMgmtEnvMonTableEntry
        MAX-ACCESS        not-accessible
        STATUS            current
        DESCRIPTION                
        "each entry has the data monitoring about environmental sensors."
        INDEX  { acsPowerMgmtEnvMonTablePortNumber, acsPowerMgmtEnvMonTablePduIndex, acsPowerMgmtEnvMonTableIndex }
::= { acsPowerMgmtEnvMonTable 1 }

AcsPowerMgmtEnvMonTableEntry ::= SEQUENCE  {
        acsPowerMgmtEnvMonTablePortNumber    InterfaceIndex,  -- number of serial port
        acsPowerMgmtEnvMonTablePduIndex      InterfaceIndexOrZero, -- number of PDU
        acsPowerMgmtEnvMonTableIndex         InterfaceIndexOrZero, -- index
	acsPowerMgmtEnvMonTableName          DisplayString,   -- sensor name 
        acsPowerMgmtEnvMonTablePduId         DisplayString,   -- PDU identification
	acsPowerMgmtEnvMonTablePortName      DisplayString,   -- Serial Port Name
	acsPowerMgmtEnvMonTableType          INTEGER,         -- environmental sensor type 
	acsPowerMgmtEnvMonTableStatus	     INTEGER,	      -- state of digital sensor
	acsPowerMgmtEnvMonTableValue	     Integer32,	      -- value
	acsPowerMgmtEnvMonTableMaxValue	     Integer32	      -- max value
}
	
acsPowerMgmtEnvMonTablePortNumber OBJECT-TYPE
        SYNTAX            InterfaceIndex
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "Number of serial port when the PDU is connected."
::= { acsPowerMgmtEnvMonTableEntry 1 }

acsPowerMgmtEnvMonTablePduIndex OBJECT-TYPE
        SYNTAX            InterfaceIndexOrZero
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "A PDU position in the chain."
::= { acsPowerMgmtEnvMonTableEntry 2 }

acsPowerMgmtEnvMonTableIndex OBJECT-TYPE
        SYNTAX            InterfaceIndexOrZero
        MAX-ACCESS        read-only
        STATUS            current
        DESCRIPTION
        "envmon sensor index."
::= { acsPowerMgmtEnvMonTableEntry 3 }

acsPowerMgmtEnvMonTableName OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "envmon sensor name."
::= { acsPowerMgmtEnvMonTableEntry 4 }

acsPowerMgmtEnvMonTablePduId  OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "PDU identification."
::= { acsPowerMgmtEnvMonTableEntry 5 }

acsPowerMgmtEnvMonTablePortName OBJECT-TYPE
        SYNTAX             DisplayString
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Name of serial port when the PDU is connected."
::= { acsPowerMgmtEnvMonTableEntry 6 }

acsPowerMgmtEnvMonTableType OBJECT-TYPE
	SYNTAX  INTEGER {
		temp-internal (1),
		temperature (2),
		humidity (3),
		air-flow (4),
		smoke (5),
		dry-concact (6),
		water-level (7),
		motion (8),
		unplugged (9),
		unknown (10)
	}
	MAX-ACCESS      read-only
	STATUS          current
	DESCRIPTION     "The type of environmental monitor."
::= { acsPowerMgmtEnvMonTableEntry 7 }

acsPowerMgmtEnvMonTableStatus OBJECT-TYPE
	SYNTAX  INTEGER {
		normal(1),
		triggered(2),
		not-applicable(3)
	}
	MAX-ACCESS      read-only
	STATUS          current
	DESCRIPTION     "Status of digital sensors:
		Dry-Contact, Water level, Smoke sensor, Motion sensor."
::= { acsPowerMgmtEnvMonTableEntry 8 }

acsPowerMgmtEnvMonTableValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu." 
::= { acsPowerMgmtEnvMonTableEntry 9 }

acsPowerMgmtEnvMonTableMaxValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu." 
::= { acsPowerMgmtEnvMonTableEntry 10 }

acsPowerMgmtOutElecMonTable OBJECT-TYPE
        SYNTAX             SEQUENCE OF AcsPowerMgmtOutElecMonTableEntry
        MAX-ACCESS         not-accessible
        STATUS             current
        DESCRIPTION
        "This table contains the information about data monitoring of outlets."
::= { acsPowerMgmt 11 }
 
acsPowerMgmtOutElecMonTableEntry  OBJECT-TYPE
        SYNTAX            AcsPowerMgmtOutElecMonTableEntry
        MAX-ACCESS        not-accessible
        STATUS            current
        DESCRIPTION                
        "each entry has the information about the outlet."
        INDEX             { acsPowerMgmtOutElecMonTablePortNumber,
                            acsPowerMgmtOutElecMonTablePduNumber,
                            acsPowerMgmtOutElecMonTableNumber }
::= { acsPowerMgmtOutElecMonTable 1 }

AcsPowerMgmtOutElecMonTableEntry ::= SEQUENCE  {
        acsPowerMgmtOutElecMonTablePortNumber   InterfaceIndex, -- serial port #
        acsPowerMgmtOutElecMonTablePduNumber    InterfaceIndex,     
        acsPowerMgmtOutElecMonTableNumber       InterfaceIndex, -- outlet number in PDU
	acsPowerMgmtOutElecMonTableCurrentValue Integer32,	     -- actual value for current
	acsPowerMgmtOutElecMonTableCurrentMax   Integer32,	     -- max detected value for current
	acsPowerMgmtOutElecMonTableCurrentMin   Integer32,	     -- min detected value for current
	acsPowerMgmtOutElecMonTableCurrentAvg   Integer32,	     -- average value for current
	acsPowerMgmtOutElecMonTableCurrentReset INTEGER,      -- reset max, min and avg values of current
	acsPowerMgmtOutElecMonTablePowerValue   Integer32,	     -- actual value for power
	acsPowerMgmtOutElecMonTablePowerMax     Integer32,	     -- max detected value for power
	acsPowerMgmtOutElecMonTablePowerMin     Integer32,	     -- min detected value for power
	acsPowerMgmtOutElecMonTablePowerAvg     Integer32,	     -- average value for power
	acsPowerMgmtOutElecMonTablePowerReset   INTEGER,	     -- reset max, min and avg values of power
	acsPowerMgmtOutElecMonTableVoltageValue Integer32,      -- actual value for voltage
	acsPowerMgmtOutElecMonTableVoltageMax   Integer32,	     -- max detected value for voltage
	acsPowerMgmtOutElecMonTableVoltageMin   Integer32,	     -- min detected value for voltage
	acsPowerMgmtOutElecMonTableVoltageAvg   Integer32,	     -- average value for voltage
	acsPowerMgmtOutElecMonTableVoltageReset INTEGER,      -- reset max, min and avg values of voltage
	acsPowerMgmtOutElecMonTablePowerFactorValue Integer32,  -- actual value for power factor
	acsPowerMgmtOutElecMonTablePowerFactorMax   Integer32,  -- max detected value for power factor
	acsPowerMgmtOutElecMonTablePowerFactorMin   Integer32,  -- min detected value for power factor
	acsPowerMgmtOutElecMonTablePowerFactorAvg   Integer32,  -- avg value for power factor
	acsPowerMgmtOutElecMonTablePowerFactorReset INTEGER,   -- reset max, min and avg values of power factor
	acsPowerMgmtOutElecMonTableAlarm	     INTEGER	    -- outlet alarm status 
}

acsPowerMgmtOutElecMonTablePortNumber OBJECT-TYPE
        SYNTAX             InterfaceIndex
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Serial Port number."
::= { acsPowerMgmtOutElecMonTableEntry 1 }

acsPowerMgmtOutElecMonTablePduNumber OBJECT-TYPE
        SYNTAX             InterfaceIndex
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Index."
::= { acsPowerMgmtOutElecMonTableEntry 2 }

acsPowerMgmtOutElecMonTableNumber OBJECT-TYPE
        SYNTAX             InterfaceIndex
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Number of the outlet in the PDU."
::= { acsPowerMgmtOutElecMonTableEntry 3 }

acsPowerMgmtOutElecMonTableCurrentValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of outlet current sensor.( A x 10 )" 
::= { acsPowerMgmtOutElecMonTableEntry 4 }

acsPowerMgmtOutElecMonTableCurrentMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of outlet current sensor.( A x 10 )" 
::= { acsPowerMgmtOutElecMonTableEntry 5 }

acsPowerMgmtOutElecMonTableCurrentMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of outlet current sensor.( A x 10 )" 
::= { acsPowerMgmtOutElecMonTableEntry 6 }

acsPowerMgmtOutElecMonTableCurrentAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for outlet current sensor.( A x 10 )" 
::= { acsPowerMgmtOutElecMonTableEntry 7 }

acsPowerMgmtOutElecMonTableCurrentReset OBJECT-TYPE
        SYNTAX        INTEGER {
                noAction(1),
                reset(2)
        }
        MAX-ACCESS         read-write
        STATUS             current
        DESCRIPTION
        "Reset max, min and avertage values of outlet current."
::= { acsPowerMgmtOutElecMonTableEntry 8 }

acsPowerMgmtOutElecMonTablePowerValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of outlet power comsumption sensor.( W x 10 )" 
::= { acsPowerMgmtOutElecMonTableEntry 9 }

acsPowerMgmtOutElecMonTablePowerMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of outlet power comsumption sensor.( W x 10 )" 
::= { acsPowerMgmtOutElecMonTableEntry 10 }

acsPowerMgmtOutElecMonTablePowerMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of outlet power comsumption sensor.( W x 10 )" 
::= { acsPowerMgmtOutElecMonTableEntry 11 }

acsPowerMgmtOutElecMonTablePowerAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for outlet power comsumption sensor.( W x 10 )" 
::= { acsPowerMgmtOutElecMonTableEntry 12 }

acsPowerMgmtOutElecMonTablePowerReset OBJECT-TYPE
        SYNTAX        INTEGER {
                noAction(1),
                reset(2)
        }
        MAX-ACCESS         read-write
        STATUS             current
        DESCRIPTION
        "Reset max, min and avertage values of outlet power comsumption."
::= { acsPowerMgmtOutElecMonTableEntry 13 }

acsPowerMgmtOutElecMonTableVoltageValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of outlet voltage sensor.( V )" 
::= { acsPowerMgmtOutElecMonTableEntry 14 }

acsPowerMgmtOutElecMonTableVoltageMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of outlet voltage sensor.( V )" 
::= { acsPowerMgmtOutElecMonTableEntry 15 }

acsPowerMgmtOutElecMonTableVoltageMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of outlet voltage sensor.( V )" 
::= { acsPowerMgmtOutElecMonTableEntry 16 }

acsPowerMgmtOutElecMonTableVoltageAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for outlet voltage sensor.( V )" 
::= { acsPowerMgmtOutElecMonTableEntry 17 }

acsPowerMgmtOutElecMonTableVoltageReset OBJECT-TYPE
        SYNTAX        INTEGER {
                noAction(1),
                reset(2)
        }
        MAX-ACCESS         read-write
        STATUS             current
        DESCRIPTION
        "Reset max, min and avertage values of outlet voltage."
::= { acsPowerMgmtOutElecMonTableEntry 18 }

acsPowerMgmtOutElecMonTablePowerFactorValue OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Actual value of outlet power-factor sensor.( PF x 100 )" 
::= { acsPowerMgmtOutElecMonTableEntry 19 }

acsPowerMgmtOutElecMonTablePowerFactorMax OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Max detected value of outlet power-factor sensor.( PF x 100 )" 
::= { acsPowerMgmtOutElecMonTableEntry 20 }

acsPowerMgmtOutElecMonTablePowerFactorMin OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Min detected value of outlet power-factor sensor.( PF x 100 )" 
::= { acsPowerMgmtOutElecMonTableEntry 21 }

acsPowerMgmtOutElecMonTablePowerFactorAvg OBJECT-TYPE
        SYNTAX             Integer32
        MAX-ACCESS         read-only
        STATUS             current
        DESCRIPTION
        "Average value for outlet power-factor sensor.( PF x 100 )" 
::= { acsPowerMgmtOutElecMonTableEntry 22 }

acsPowerMgmtOutElecMonTablePowerFactorReset OBJECT-TYPE
        SYNTAX        INTEGER {
                noAction(1),
                reset(2)
        }
        MAX-ACCESS         read-write
        STATUS             current
        DESCRIPTION
        "Reset max, min and avertage values of outlet power-factor."
::= { acsPowerMgmtOutElecMonTableEntry 23 }

acsPowerMgmtOutElecMonTableAlarm OBJECT-TYPE
        SYNTAX       INTEGER {
			normal (1),
			blow-fuse (2),
			hw-ocp (3),
			high-critical (4),
			high-warning (5),
			low-warning (6),
			low-critical (7)
                    }
        MAX-ACCESS      read-only
        STATUS          current
        DESCRIPTION     "Show the outlet alarm status."
::= { acsPowerMgmtOutElecMonTableEntry 24 }

END